Cable Size Calculator
Free online cable sizing calculator for Australian electrical installations - AS/NZS 3008 compliant
Free Cable Size Calculator
Enter your circuit parameters below to calculate the recommended cable size based on AS/NZS 3008 current carrying capacity and voltage drop requirements.
This is an estimate based on simplified calculations. For detailed analysis with all derating factors, use our professional calculator.
Get Full Calculation ReportHow to Use This Cable Size Calculator
Our cable size calculator helps you select the correct cable size for Australian electrical installations per AS/NZS 3008. Simply enter your load current, cable length, and installation method above to get an instant recommendation. This guide explains the cable sizing methodology and when you might need our full professional calculator.
Why Use a Cable Size Calculator?
Selecting the correct cable size ensures safe operation, prevents overheating, minimizes voltage drop, and complies with Australian standards. A cable size calculator automates the complex calculations involving current carrying capacity, derating factors, and voltage drop limits specified in AS/NZS 3008.
Understanding Current Carrying Capacity
- Conductor material - Copper has approximately 1.6 times the conductivity of aluminium
- Conductor cross-sectional area - Larger cables can carry more current
- Insulation type - PVC (70°C), V-90 (90°C), XLPE (90°C) have different temperature ratings
- Installation method - How well the cable can dissipate heat
Key Principle: The cable's derated current carrying capacity must be greater than or equal to the design current (Ib) of the circuit. Mathematically: Iz × derating factors ≥ Ib
Derating Factors Explained
Temperature Derating (Table 27)
45°C ×0.91 · 50°C ×0.82 · 55°C ×0.71
Grouping/Bunching (Table 22)
2 circuits ×0.80 · 3 ×0.70 · 4 ×0.65 · 6 ×0.57
Depth of Burial (Table 28)
0.5m none · 0.8m ×0.97 · 1.0m ×0.95 · 1.25m ×0.93
Voltage Drop Calculations
- Consumer mains: Maximum 2% from point of supply to main switchboard
- Final subcircuits: Maximum 5% from point of supply to any point in the installation
Single-phase: Vd = (mV/A/m × Ib × L × 2) / 1000Three-phase: Vd = (mV/A/m × Ib × L × √3) / 1000
Cable Selection Methodology
- Determine the design current Ib
- Select the protective device rating In (≥ Ib)
- Identify installation conditions
- Calculate the total derating factor
- Select the minimum cable size with Iz × derating ≥ In
- Check voltage drop against the limits
- Verify fault current withstand
AS/NZS 3008 Cable Current Ratings Reference
Current carrying capacity for copper and aluminium cables with thermoplastic (PVC) insulation at 40°C ambient temperature. Based on AS/NZS 3008.1.1 Table 4 (enclosed in conduit).
| Size (mm²) | Current (A) | mV/A/m |
|---|---|---|
| 1 | 14 | 44 |
| 1.5 | 17.5 | 29 |
| 2.5 | 24 | 18 |
| 4 | 32 | 11 |
| 6 | 41 | 7.3 |
| 10 | 57 | 4.4 |
| 16 | 76 | 2.8 |
| 25 | 101 | 1.8 |
| 35 | 125 | 1.3 |
| 50 | 151 | 0.93 |
| 70 | 192 | 0.63 |
| 95 | 232 | 0.46 |
| 120 | 269 | 0.36 |
| 150 | 300 | 0.29 |
| 185 | 341 | 0.25 |
| 240 | 400 | 0.195 |
| Size (mm²) | Current (A) | mV/A/m |
|---|---|---|
| 16 | 57 | 4.6 |
| 25 | 75 | 2.9 |
| 35 | 92 | 2.1 |
| 50 | 112 | 1.55 |
| 70 | 140 | 1.1 |
| 95 | 170 | 0.78 |
| 120 | 200 | 0.61 |
| 150 | 230 | 0.5 |
| 185 | 265 | 0.41 |
| 240 | 315 | 0.32 |
| 300 | 360 | 0.265 |
Aluminium conductors are typically only used for sizes 16mm² and above.
| Ambient Temp | PVC 75°C | PVC 90°C | XLPE 90°C |
|---|---|---|---|
| 35°C | 1.04 | 1.04 | 1.04 |
| 40°C | 1 | 1 | 1 |
| 45°C | 0.91 | 0.96 | 0.96 |
| 50°C | 0.82 | 0.93 | 0.93 |
| 55°C | 0.71 | 0.89 | 0.89 |
| 60°C | 0.58 | 0.84 | 0.84 |
Professional Features
Why Use CableHero's Full Calculator?
Our professional cable sizing software goes beyond basic calculations to give you accurate, compliant results every time.
All Derating Factors
- Temperature derating (Table 27)
- Grouping factors (Table 22)
- Burial depth (Table 28)
- Soil resistivity (Table 29)
Voltage Drop Analysis
- Accurate mV/A/m values
- Single & three-phase
- Compliance indicators
- Any cable length
Fault Loop Impedance
- Zs calculations
- Protection coordination
- MCB/RCD verification
- Earth fault current
PDF Reports
- Professional format
- Full calculation breakdown
- Certification ready
- Custom branding
Complete Cable Database
- Copper & Aluminium
- PVC, XLPE, EPR
- All installation methods
- Manufacturer data
Project Management
- Save calculations
- Organize by project
- Cable schedules
- Revision history
Frequently Asked Questions
Cable Sizing Questions Answered
How do I calculate cable size for my electrical installation?⌄
To calculate cable size according to AS/NZS 3008, you need to: 1) Determine your load current, 2) Identify the installation method, 3) Apply derating factors for temperature, grouping, and burial depth, 4) Select a cable with adequate current carrying capacity, 5) Verify voltage drop is within the 5% limit, and 6) Check fault current withstand capability. Our calculator above handles steps 4-5 automatically.
What cable size do I need for 32 Amps?⌄
For a 32 Amp load with copper conductors and PVC insulation, you need at least 4mm² for short runs (under 15m) or 6mm² for typical installations up to 30m. For longer runs, 10mm² may be required to keep voltage drop under 5%. The exact size depends on installation method, ambient temperature, and any grouping with other cables. Use our calculator for your specific conditions.
What cable size do I need for 20 Amps?⌄
For a 20 Amp circuit, 2.5mm² copper is typically adequate for short runs in conduit. For runs over 20 meters, consider using 4mm² to minimize voltage drop. If the cable is bunched with other circuits or in high ambient temperatures, derating may require upsizing to 4mm² regardless of length.
What is AS/NZS 3008?⌄
AS/NZS 3008 (Electrical installations - Selection of cables) is the Australian/New Zealand Standard that specifies requirements for selecting cables. It covers current carrying capacity tables for different installation methods, voltage drop calculation methods using mV/A/m values, derating factors for various conditions, and cable construction requirements. Part 1.1 covers cables for AC voltages up to and including 0.6/1kV.
What are cable derating factors?⌄
Derating factors reduce a cable's rated current capacity based on installation conditions that affect heat dissipation. Key factors include: ambient temperature (Table 27) - higher temps mean more derating, cable grouping (Table 22) - multiple cables together generate more heat, burial depth (Table 28) - deeper burial reduces heat dissipation, and soil thermal resistivity (Table 29) - affects buried cable ratings. All applicable factors are multiplied together.
What is the maximum voltage drop allowed in Australia?⌄
According to AS/NZS 3000 (Wiring Rules), the maximum voltage drop from the point of supply to any point in the installation should not exceed 5% for final subcircuits under normal conditions. For consumer mains (from supply to main switchboard), the typical limit is 2%. These limits ensure equipment operates correctly and efficiently.
Copper vs aluminium cables - which should I use?⌄
Copper has about 1.6x the conductivity of aluminium, so copper cables are smaller for the same current capacity. Copper is preferred for most installations due to better conductivity, easier termination, and no galvanic corrosion issues. Aluminium is mainly used for large feeders (95mm² and above) where cost savings are significant. Aluminium requires special terminations and is not recommended for sizes below 16mm².
How does installation method affect cable sizing?⌄
Installation method significantly affects current ratings because it determines heat dissipation capability. Cables in free air have the highest ratings. Cables in conduit have reduced ratings due to restricted air flow. Buried cables ratings depend on soil conditions and depth. Cables on trays have good ratings with proper spacing. AS/NZS 3008 provides separate current rating tables for each installation method.
Ready for Professional Cable Sizing?
Join thousands of Australian electricians and engineers using CableHero for accurate, AS/NZS 3008 compliant calculations with detailed PDF reports.